| Model | MP41P (Positive) | ||
| Rated pressure range | 0.000 ~ 1.000 MPa | ||
| Setting pressure range | -0.100 ~ 1.000 MPa | ||
| Withstand pressure | 1.5 MPa | ||
| Fluid | Air, Non-corrosive gases, incombustible gases | ||
| Set pressure resolution | MPa | 0.001 | |
| kgf/cm² | 0.01 | ||
| bar | 0.01 | ||
| psi | 0.1 | ||
| Power supply voltage | 12 to 24V DC ±10%, Ripple(P-P) 10% or less | ||
| current consumption | ≦ 40mA(With no load) | ||
| Switch output |
NPN open collector Max. load current : 125mA Max. supply voltage : 30V DC Residual votage : ≦ 1.5V (load current 125mA) |
PNP open collector Max. load current : 125mA Max. supply voltage : 24V DC Residual votage : ≦ 1.5V (load current 125mA) |
|
| Repeatability(Switch output) | ≦ ±0.2% F.S. ±1 digit | ||
| Hysteresis | One point set mode | Adjustable | |
| Hysteresis mode | |||
| Window com parat or mode | |||
| Response time | Chattering-function : 0.05s, 0.25s, 0.5s, 1s, 2s, 3s selection | ||
| Output short circuit protection | Yes | ||
| 7 segment LED display | Two color(Red/Green) main & unit display. Orange sub-display(Sampling rate : 5 times/1 sec.) |
||
| indicator accuracy | ≦ ±0.2% F.S. ±1 digit(ambient temperature : 25 ±3℃) | ||
| Switch ON Indicator | Orange OUT 1 Indicator | ||
| Environment | Encolsure | IP40 | |
| Ambient temp. range | Operation:0~50℃, Storage:-10~60℃ (No condensation or freezing) | ||
| Ambient humidity range | Operation/Storage:35~85% RH (No condensation) | ||
| Withstand voltage | 100V AC in 1-min(between case and lead wire) | ||
| Insulation resistanace | 50MΩ min.(at 500V DC between case and lead wire) | ||
| Vibration | Total amplitude 1.5mm or 10G,10Hz-150Hz-10Hz scan for 1 minute,two hours each direction of X,Y and Z | ||
| Shock | 100m/s²(10G),3 times each in direction of X,Y and Z | ||
| Temperature characteristic | ≦ ±2% F.S. of detected pressure (25℃) at temp. Range of 0~50℃ | ||
| Lead wire | Oil-resistance cable(0.15mm²) | ||
| Weight | Approx 65g(with 2-meter lead wire),Approx 30g(with male connector) | ||